Legionella Legislation and HSE Guidance: What It Means for You

How many sites?

Your quote by email within one working day · No obligation

Used only for this enquiry. No marketing lists. Privacy notice

Is a legionella risk assessment a legal requirement? Yes, if you are an employer, self-employed or in control of premises. You must assess the risk from legionella and, if there is one, control it. COSHH requires it, and the HSE's Approved Code of Practice L8 says how. There is no "legionella certificate" in law. What you need is a written risk assessment that matches your building today, and records that show you acted on it.

Need the assessment itself? A fixed price within one working day.

Not sure if you need one? Who needs one

1. What it all means for you

Take away the Acts, the regulations and the guidance, and five things are left for anyone who runs a workplace or controls a building with water in it:

  1. Assess the risk. Someone competent looks at every water system and says where legionella could grow and who could breathe it in.
  2. Put someone in charge. Appoint a responsible person to run the controls day to day, with a deputy.
  3. Write down how the risk is controlled. Where the assessment finds a risk, a written scheme says what is checked, how, how often and by whom.
  4. Do the checks and keep the records. Temperatures, flushing, cleaning and inspections, each one dated and kept.
  5. Review it. Regularly, and at once when something changes.

The rest of this page says where each duty comes from. What to do, step by step, and who does what:

What your business needs to do

Your responsibilities, role by role

2. Who the duty falls on

ACOP L8 names the duty holder. It is one of three people. The employer, where the business puts employees or others at risk. A self-employed person, where they put themselves or others at risk. Or the person in control of premises or systems in connection with work, such as a landlord who lets a building but keeps responsibility for maintaining it.

So the duty is not about the size of the business. A two-chair dental practice, a village school, a 200-bed care home and a managing agent with one communal tank all have it. What changes is how much there is to assess.

Need an assessment? A fixed price within one working day

Get my price

3. The Health and Safety at Work etc. Act 1974

The Act is the foundation. Section 2 says employers must ensure the health, safety and welfare of their employees, so far as is reasonably practicable. Section 3 extends that to people who are not employees but could be affected by the business: customers, patients, residents, visitors, contractors. Section 4 puts duties on people who control non-domestic premises, including where they are let to others. The HSE says these general duties extend to the risk from legionella.

One point the HSE makes plainly: a section 3 duty cannot be passed on by contract. You can employ a contractor to do the work, but the duty to see that the risk is managed stays with you.

4. The COSHH Regulations 2002

The Control of Substances Hazardous to Health Regulations 2002 are where the risk assessment itself comes from. Legionella is a biological agent, and COSHH requires a "suitable and sufficient" assessment of the risk from it, then prevention of exposure where possible, control where not, monitoring that the controls work, and records.

ACOP L8 says who may do the assessment: the person must be competent (paragraph 29). Neither COSHH nor L8 names a qualification. In practice that means someone with the skills, knowledge and experience for the water systems on your site. For a business, we recommend a professional assessor. Who can carry one out, in more detail:

Who can carry one out

5. The Management of Health and Safety at Work Regulations 1999

The Management Regulations sit alongside COSHH. They require every employer to assess the risks to employees and others, to review the assessment regularly and make any changes it shows are needed, and to have access to competent help in applying health and safety legislation. For legionella, COSHH is the specific duty and the Management Regulations are the framework around it.

Need an assessment? A fixed price within one working day

Get my price

6. ACOP L8: the Approved Code of Practice

Legionnaires' disease: The control of legionella bacteria in water systems (L8, fourth edition, 2013) is the HSE's Approved Code of Practice. It applies to any work activity or premises where water is used or stored in a way that could produce breathable droplets and a reasonably foreseeable risk of legionella, and it applies to employers, the self-employed and people in control of premises.

An ACOP is not legislation itself, but it has a special legal status. If you are prosecuted and it is proved you did not follow the Code, you must show you complied some other way. If you cannot, a court will find you at fault.

What L8 asks of a duty holder, in order:

  1. Identify and assess the sources of risk, using a competent person, considering the whole system including parts used only now and then, with an asset register and a schematic diagram for anything complex.
  2. Prevent or control the risk: avoid water between 20°C and 45°C, stop stagnation, keep the system clean, control any spray.
  3. Appoint a responsible person (section 9 below).
  4. Write a scheme of control that says how the risks are managed day to day, and who does what.
  5. Implement, manage and monitor the precautions.
  6. Keep records of the assessment, the scheme and every check.
  7. Review the assessment regularly, and whenever there is reason to think it is no longer valid.

The fourth edition dropped the "review every two years" line of the third edition. Review is now "regularly", and at once when anything changes: the water system or its use, the use of the building, new information, checks showing controls are failing, a change of key people, or a case of the disease. How often in practice, and where the two-year idea came from:

How often you need one

7. HSG274 Parts 1, 2 and 3

HSG274 is the HSE's technical guidance that used to be Part 2 of L8. It is guidance, not an ACOP: following it is not compulsory, but if you do you will normally be doing enough to comply, and inspectors refer to it. It comes in three parts.

Part 1: evaporative cooling systems. Cooling towers and evaporative condensers. Design, water treatment, cleaning, monitoring and the notification duty. Tell us if you have a cooling tower and we come back to you with a quote within one working day, because these systems and the rules around them are different from a building's taps and showers.

Part 2: hot and cold water systems (second edition, 2024). This is the part that applies to most workplaces. Its key numbers:

  • cold water below 20°C where possible
  • hot water stored at 60°C or above, and 50°C at the tap within one minute (55°C in healthcare)
  • little-used outlets flushed weekly
  • cold water tanks and calorifiers (hot water cylinders) inspected yearly
  • sentinel outlet temperatures checked monthly
  • showers cleaned and descaled quarterly, or as the assessment says
  • TMVs serviced yearly, or as the assessment says

Legionella temperatures, explained

It also lists what a risk assessment should contain, and says the review must be regular and prompt when the assessment may no longer be valid.

Part 3: other risk systems. Spa pools and hot tubs, humidifiers, air washers, emergency showers and eye washes, indoor fountains and water features, vehicle washes, dental unit waterlines and similar. Where a site has one of these, your assessor covers it. For a spa pool or a vehicle wash we come back to you with a quote within one working day.

Need an assessment? A fixed price within one working day

Get my price

8. BS 8580-1:2019

BS 8580-1:2019 Water quality. Risk assessments for Legionella control. Code of practice is the British Standard for how a legionella risk assessment is carried out and written. It is not legislation and not HSE guidance, but HSG274 Part 2 points duty holders to it, and a good assessor works to it. Our assessments are written to BS 8580-1.

9. The responsible person

ACOP L8 says the duty holder should appoint someone to take day-to-day responsibility for controlling the legionella risk: the "responsible person". They need enough authority, competence and knowledge of the installation to make sure the checks and controls happen on time. They can be you, a member of staff, or an outside contractor, and a self-employed duty holder who is competent may appoint themselves. Whoever it is, they should be trained, with a record of the training, and there should be a named deputy for holidays and absence.

Your report names the responsible person and lists what they are expected to do and how often. If nobody has been appointed yet, the assessor says so, and that is usually the first action on the list.

What the responsible person does

10. Cooling towers: the 1992 notification duty

If you have a cooling tower or an evaporative condenser, the Notification of Cooling Towers and Evaporative Condensers Regulations 1992 apply as well. Every person with any control of the premises must make sure the local authority for the area has been notified in writing before the device is used. The notice gives the address, the name and contact details of a person in control, how many devices there are and where each one is. Any change must be notified within one month, and the council must be told as soon as reasonably practicable when a device stops being used. A seasonal shutdown or a stop for maintenance does not count as stopping use.

The forms come from your council's environmental health department. Tell us if you have a tower and we come back to you with a quote within one working day.

Get my price

11. Records, review and RIDDOR

Records. With five or more employees you must record the significant findings of the assessment, the precautions and the treatments. With fewer than five you don't have to write anything down, but the HSE says it is useful to. Keep the assessment and the written scheme for as long as they are current and for at least two years after that. Keep the results of every monitoring inspection, test or check, with dates, for at least five years.

Review. Regularly, and at once whenever there is reason to think the assessment is no longer valid (section 6). Write the review date into the assessment, and the changes that would bring it forward.

RIDDOR. A case of legionellosis in an employee who has worked on cooling towers or hot water systems likely to be contaminated must be reported under the Reporting of Injuries, Diseases and Dangerous Occurrences Regulations 2013.

Need an assessment? A fixed price within one working day

Get my price

12. Landlords and rented homes

Landlords have a legal duty to assess the risk from legionella. HSE's guidance says a landlord can carry out the assessment themselves if they are competent to.

Blocks of flats with communal tanks, pumped cold water or shared hot water plant are different. The duty falls on whoever controls the communal system, usually the freeholder or managing agent. Those systems are assessed like any workplace system. We price blocks of flats and managing agents' portfolios.

Landlord or letting agent? For houses and flats, use DwellFlow. It is a landlord legionella risk assessment that you carry out yourself on your phone, with the report written by AI. It is free to start and £9.99 ex VAT per property. There is also free legionella training for landlords.

Legionella for landlords

Go to DwellFlow

Get my price for a block of flats

13. What happens if you don't

Three things, in the order they tend to happen.

Someone asks for it. The CQC at a dental practice or care home, the HSE or the academy trust's auditor at a school, an insurer at renewal, a landlord at lease review, a buyer at sale, a tenant's solicitor after a complaint. "We haven't got one" then becomes a finding of its own.

An inspector visits. The HSE and local authority environmental health officers enforce health and safety legislation. They can serve an improvement notice (fix it by a date) or a prohibition notice (stop using it now), and they can prosecute. Because L8 is an Approved Code of Practice, not having assessed the risk at all is hard to defend.

Someone gets ill. Legionnaires' disease is a notifiable disease, so a case is investigated and traced back to a source. The people most at risk are over 45, smokers, heavy drinkers, and anyone with lung, kidney or heart disease, diabetes or a weakened immune system: the residents of a care home, the patients in a waiting room, the older staff member. That is why the legislation exists.

The fix is not complicated. Assess the risk, act on the list, keep the records, review when things change.

When it goes wrong: real HSE cases

Questions

14. Questions people ask

Is a legionella risk assessment a legal requirement?

Yes, if you are an employer, self-employed or in control of premises: you must assess the risk from legionella under COSHH and follow ACOP L8. The assessment must be carried out by someone competent. For a business, have it carried out by a professional assessor.

Get my price

What is ACOP L8?

The HSE's Approved Code of Practice on legionella (fourth edition, 2013). It is not legislation itself, but if you are prosecuted and did not follow it, you must show you complied another way. It sets out the assessment, the responsible person, the written scheme, records and review.

Get my price

What is HSG274?

The HSE's technical guidance in three parts: Part 1 cooling towers, Part 2 hot and cold water systems (2024 edition), Part 3 other systems such as spa pools. Following it is not compulsory, but doing so normally means you comply, and inspectors refer to it.

Get my price

Who is the responsible person for legionella?

The person the duty holder appoints to take day-to-day charge of controlling the risk, under ACOP L8. They need the authority, competence and knowledge of the site to make sure the checks happen, with a trained deputy.

Your legionella responsibilities

Get my price

Do I have to notify my cooling tower?

Yes. Under the 1992 Regulations the local authority must be notified in writing before a cooling tower or evaporative condenser is used, told of any change within a month, and told when it stops being used. Forms come from environmental health.

Get my price

Does a landlord need a legionella risk assessment?

Yes. Landlords have a legal duty to assess the risk from legionella. HSE's guidance says a landlord can carry out the assessment themselves if they are competent to. Communal systems in blocks are assessed like any workplace system. For a rented house or flat, use our sister site, DwellFlow. It is a legionella risk assessment for landlords that you carry out yourself on your phone, with the report written by AI.

Legionella for landlords

Go to DwellFlow

How long do I keep legionella records?

Keep the assessment and written scheme while they are current and for at least two years after. Keep the results of every monitoring inspection, test or check, with dates, for at least five years. ACOP L8 paragraph 72.

Get my price

Is there a legionella certificate?

No. Health and safety legislation does not require or recognise a "legionella certificate". What it requires is a written risk assessment that matches the building today, and records showing you acted on it.

Is there a legionella certificate?

Get my price

Who are the LCA?

The Legionella Control Association (LCA) is a UK body for companies that provide legionella control services. It was founded in 1999 by the Water Management Society and the British Association for Chemical Specialities (now the BCA). Member companies are audited when they join and every year after that. The audit is against the LCA Code of Conduct and its Service Standards, and covers only the services they have registered. A company is only listed while it appears on the LCA directory.

Your assessment is carried out by our City & Guilds qualified, LCA registered risk assessors. The registration is shown on your quotation, and you can check it on the LCA directory.

Registration shows a company works to an audited standard. It is not a guarantee, and the LCA does not assess individual staff, so we also show you exactly what is included and what happens on the day. Read more

About 2 minutes · No account · No obligation

Not sure if you need one?

Who are the LCA?

The Legionella Control Association (LCA) is a UK body for companies that provide legionella control services. It was founded in 1999 by the Water Management Society and the British Association for Chemical Specialities (now the BCA). Member companies are audited when they join and every year after that. The audit is against the LCA Code of Conduct and its Service Standards, and covers only the services they have registered. A company is only listed while it appears on the LCA directory.

Your assessment is carried out by our City & Guilds qualified, LCA registered risk assessors. The registration is shown on your quotation, and you can check it on the LCA directory.

Registration shows a company works to an audited standard. It is not a guarantee, and the LCA does not assess individual staff, so we also show you exactly what is included and what happens on the day.

Read more