What Temperature Kills Legionella?
Legionella grows in water between 20°C and 45°C. At 60°C and above it is killed, given time. That is why HSE guidance asks for hot water to be stored at 60°C or hotter. It should reach the taps at 50°C or more within one minute, or 55°C in healthcare premises. Cold water should stay below 20°C, and run cold within two minutes.
Heat kills legionella over time, not in an instant. So day to day, the aim is not to kill it. It is to keep all the water out of the range where it grows.
Need the assessment that sets your checks? A fixed price within one working day.
The temperatures at a glance
| Where | Temperature | HSE source |
|---|---|---|
| Where legionella grows | 20°C to 45°C | ACOP L8 |
| Hot water stored in a cylinder or calorifier | 60°C or above | HSG274 Part 2, 2.6 |
| Hot water at the tap | 50°C or above within 1 minute | HSG274 Part 2, 2.6 |
| Hot water at the tap in healthcare premises | 55°C or above within 1 minute | HSG274 Part 2, 2.156 |
| Hot water returning to the calorifier | 50°C or above | HSG274 Part 2, Table 2.1 |
| Cold water at the tap | Below 20°C within 2 minutes | HSG274 Part 2, Table 2.1 |
| Cold water stored in a tank | Below 20°C where possible | HSG274 Part 2, 2.6 |
| Small water heaters, up to 15 litres | 50°C to 60°C | HSG274 Part 2, 2.69 |
| Water from a thermostatic mixing valve | About 38°C to 46°C | HSG274 Part 2, 2.74 |
| Risk of scalding | Above 44°C | HSE, hot and cold water |
| Heat disinfection, every outlet | 60°C or above, run for at least 5 minutes | HSG274 Part 2, 2.133 |
What temperature kills legionella
Heat kills legionella, but it takes time as well as temperature. HSE guidance treats 60°C as the line. Hot water is stored at 60°C or above. In a large calorifier, the guidance suggests heating the whole vessel to at least 60°C for one continuous hour a day. That is because cold water coming in at the base cools the bottom.
When a hot water system is disinfected with heat, the whole calorifier is heated and the water circulated for at least an hour. Then every hot tap and appliance is run in turn, for at least five minutes at full temperature, with the water at 60°C or more. HSE guidance warns this can fail where parts of the system don't get hot enough for long enough.
Below 60°C, heat is a control, not a cure. Water at 50°C at the tap is not there to kill legionella. It is there to keep hot water out of the range where legionella multiplies.
Cold does not kill legionella either. The bacteria live in rivers and lakes in low numbers. Keeping cold water below 20°C stops them multiplying.
The catch is scalding. Water hot enough to control legionella can scald. The HSE says there is a scalding risk above 44°C. At 50°C the risk is small for most people, but it rises quickly at higher temperatures. Young children, older people and people with sensory loss are most at risk.
Hot water: 60°C stored, 50°C at the tap
Hot water should be stored at 60°C or above and reach every tap at 50°C or more within one minute of turning it on. In a system with a circulating loop, the water coming back to the calorifier should be at least 50°C.
Why the minute matters: water in the pipe to a tap cools between uses. HSE guidance asks for the pipes to each tap to be insulated and short enough for 50°C to arrive within a minute. A tap that takes longer points to a long branch or a failed circulation, where water can sit in the growth range.
The base of a hot water cylinder is where risk collects. Cold water comes in at the bottom, sediment settles there, and the water can sit below 60°C. That is why cylinders are drained and inspected, and why the thermostat should be as close to 60°C as practicable without going below it.
Combi boilers and instant heaters store little or no hot water, which the HSE says lowers the risk. HSE guidance asks small point-of-use heaters to reach 50°C to 60°C, and says the people using them should be told not to adjust them.
Care homes and healthcare: 55°C, and mixing valves
Where people are more vulnerable, HSE guidance raises the tap temperature. In healthcare premises, hot water should reach the outlets at 55°C within one minute. The water returning to the calorifier should not fall below 50°C.
That makes scalding a bigger worry. Where vulnerable people use baths or showers and the scalding risk is significant, HSE guidance requires a type 3 thermostatic mixing valve (TMV3). It blends hot and cold water to a safe temperature, and the person using it can't override it.
Blended water brings its own risk. A mixing valve delivers water at about 38°C to 46°C, right in the growth range. So HSE guidance asks for valves as close to the tap as possible, and for them to be maintained to keep them working.
In healthcare buildings with susceptible patients, outlets that are not used regularly may need flushing twice a week rather than weekly.
More on care homes and on TMV servicing.
Cold water: below 20°C within two minutes
Cold water should be kept below 20°C where possible. At the tap, it should drop below 20°C within two minutes of running.
Mains water usually arrives well below that. HSE guidance puts groundwater at about 12°C, and surface water between 4°C in a cold winter and 23°C in a very hot summer. The risk is the heat water picks up inside the building. Think of a tank in a warm loft, a cold pipe beside a hot one, or water standing in pipes nobody uses.
So HSE guidance asks for cold water tanks with tight lids and insulation, holding no more than a day's use. Cold pipes should be insulated and kept away from hot pipes and heating.
In an exceptionally hot summer, the incoming water may run warmer than usual, and the risk assessment may need a look.
How the checks are done
Temperatures are checked at sentinel outlets. These are the taps nearest to and furthest from the hot water heater or the cold water tank, chosen to represent the whole system. Your risk assessment names them.
- Hot taps. Run the tap with a thermometer in the water. It should reach at least 50°C within one minute, or 55°C in healthcare premises.
- Cold taps. Run the tap and watch the reading as it flushes. It should fall below 20°C within two minutes.
- The calorifier. Read the flow temperature, which should be close to 60°C but not below it, and the return, which should not be below 50°C.
- The cold water tank. Once a year, in summer, check the stored water against the incoming mains.
- Everywhere else. A rotating selection of other taps, so the whole system is profiled over time.
Every reading is recorded with who took it, the date and exactly where, so the next check can be repeated in the same place.
How often each check is done, and how to keep the log book, is on our monitoring page.
Taps and showers nobody uses
A tap or shower that stands unused lets water sit at room temperature, in the growth range. HSE guidance says outlets not in regular use should be flushed weekly for several minutes. Once started, the flushing has to be kept up and logged, because a lapse can lead to a sharp rise in legionella at the outlet.
Better still, take out the ones you don't need. Cut the pipe that fed them back to the main supply, so no dead leg is left behind.
In an empty rented home, the HSE's rule of thumb is to use every hot and cold outlet at least once a week.
When a reading is wrong
A reading out of range means the controls are not working at that point. Find out why: a thermostat set too low, a circulating pump that has failed, a long pipe run, or a tap that is hardly used. Put it right, then check again.
ACOP L8 lists checks that show the controls are no longer working as a reason to review the risk assessment. If the same reading keeps failing, the fix is usually remedial work, not more readings.
City & Guilds qualified, LCA registered assessors · Report usually within 10 to 15 working days of the visit
Questions people ask
Is 50°C hot enough to kill legionella?
It is not meant to. 50°C at the tap is a control temperature: it keeps hot water out of the 20°C to 45°C range where legionella grows. To kill it with heat, HSE guidance uses 60°C or more at every outlet, for at least five minutes.
Does hot water need to be 60°C at the tap?
No. HSE guidance asks for 60°C where hot water is stored, and at least 50°C at the tap within one minute (55°C in healthcare premises). The water at the tap is cooler because it has travelled through the pipes.
Can legionella survive in cold water?
Yes. Legionella lives in rivers and lakes in low numbers, so cold water does not kill it. Keeping cold water below 20°C stops it multiplying, which is why HSE guidance sets that limit.
What temperature should a combi boiler be set to for legionella?
High enough for the hot taps to reach at least 50°C. A combi heats water as you use it and stores little or none, which the HSE says lowers the risk. Check the temperature at the taps, and remember the scalding risk above 44°C.
What temperature should a cold water tank be?
Below 20°C where possible. HSE guidance asks for the stored water and the incoming mains to be checked once a year, in summer. Tanks should be insulated, with a tight lid, and hold no more than a day's use.
Can I turn my hot water down to save energy?
Not below the control temperatures unless another control takes over. HSE guidance allows lower hot water temperatures only with a proven alternative, such as a biocide, checked at least weekly. It is not permitted in healthcare premises with patients at higher risk.
Sources
- HSE, Hot and cold water systems
- HSE, HSG274 Part 2: The control of legionella bacteria in hot and cold water systems, paragraphs 2.4, 2.6, 2.25, 2.36, 2.37, 2.54 to 2.69, 2.74 to 2.88, 2.133, 2.134, 2.156 to 2.166 and Table 2.1
- HSE, ACOP L8: The control of legionella bacteria in water systems (fourth edition, 2013), paragraphs 11, 47 and 59
- HSE, Legionella and landlords' responsibilities
- HSE, Monitoring and keeping records
This guide explains legionella legislation and HSE guidance in plain English. It is not legal advice.